NovaEuris provides industrial equipment, instruments, food processing systems and green energy solutions for manufacturers and engineering companies across European markets.

Contact Info

  • Musterstraße 123 , 10115 Berlin
  • support@novaeuris.com

Follow Us

GF1061 Portable High Precision CT PT Analyzer with Printer – Electrical Transformer Testing Equipment

Share This Article:

Product Description

 GF1061PT PT tester is the first portable device (4.8 kg) which offers highly accurate voltage transformer tests. This allows to use GF1061PT not only for electrical performance checks, but also for class verification and calibration. It performs quick tests of all kinds of inductive voltage transformers (VTs or PTs) and capacitive voltage transformers (CVTs) for both protection and metering purposes.
Its lightweight design makes it ideal for on-site tests and calibration tasks in power system grids. As a manufacturer or testing lab you can use GF1061PT in your production facilities and test/development labs.
GF106PT voltage transformer test equipment can finish the measurements (M) and protection (P) class PT. Adopt 7 inch touch TFT color LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to download data. The GF1061PT portable PT test set is the most complete and easy-to-use testing system for PTs according to IEEEC57.13 and IEC60044 & IEC61869 standards.

Features

 Multi secondary winding test optional;

 Produce a word or PDF file test report;

 With battery optional, working one week;

 PT test, easy to test, all the tests result quickly;

 Portability: weight 4.8kg, the best light pt analyzer

 Tests such as ratio, phase, polarity, capacitive ratio;

 With thermal printer, printing test results in the field;

 Parameters such as knee point current and voltage;

 Parameters such as 10% error curve, 5% error curve;

 The data can be displayed and analyzed after transferred to PC;

 Tests of various types of measurement and protection VTs and CVTs;

 Using of advanced power technology, the test knee point reaches up to 80kV;

 No external other auxiliary equipment, stand-alone to complete all test items;

 Storage 10000 groups of test data which would not be lost if the device is power off;

Application

 Power plant;

 Electrical laboratory;

 Metrological service center;

 Voltage transformer factory;

 Power engineering commissioning company;

 Electricity power bureau & power company;

 National Metrology and testing department;

 Electrical Department of industrial and mining enterprises;

Functions
I. Voltage Transformer (PT)
1. Excitation characteristic test
2.  Transformation ratio test
3.  Polarity
4.  Ratio error, phase error
5.  Degauss
6.  Calculation of knee point value
7. burden test
8. Resistance test

Parameters

Electrical parameters
Accuracy0.02% or 0.05%
Power SupplyAC 220V±10% or AC 120V±10%, 50/60Hz or Battery
Output voltage0-100Vrms
Output current0-5Arms (20A peak-value)
Output power0-400 VA (1500 VApeak)
Automatic frequency variation range0.1-60Hz
Equivalent excitation voltage≤5000V/50KV
Accuracy≤0.02% or 0.05%
Secondary winding DC resistance measurement
Range0.1-1000Ω
Accuracy≤0.02% or 0.05%
Secondary actual load measurement
Range0.1VA-1000VA
Accuracy≤0.02%±0.1VA
CT/PT phase error measurement
Accuracy±1min (typical) / 3 min (guaranteed)
Resolution0.1min
CT ratio error measurement
Range1-50000
Accuracy≤0.02% or 0.05%
PT ratio error measurement
Range1-30000
Accuracy≤0.02% or 0.05%
LCD display7' inch TFT touch color LCD
Cable LengthPrimary 5m; Secondary 5m; others customized
Communication portUSB, RS232, WIFI
PC control softwareYes, Optional
PrinterYes, Thermal printer
Standards
Reference standardsGB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-2,6, IEC61869, ANSI/IEEE C57.13
Safety standardsGB 4793.1-2007
EMCEMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2/3/4/6
Mechanical parameters
Overall dimension (L x W x H) (mm)280 x 250 x 160
Weight (kg)≤4.5
Environmental conditions
Relative humidityRelative humidity 5%-95% not condensing
Operating temperature-10°C to +50°C
Storage temperature-20°C to +70°C
Altitude≤1000m; If the altitude is greater than 2500m, the instrument needs to be customized

Reposted for informational purposes only. Views are not ours. Stay tuned for more.