SF6 Gas Insulated Recloser General Eliminating a fault in Distribution network and optimizing a fault areaSF6 gas Insulated Vacuum Interrupter KT, NT Certificate and Korean World-Class Product Award for Magnetic Actuator MechanismBuilt-In RTU Digital Cont
| SF6 Gas Insulated Recloser |
| |
| |
| General |
| |
- Eliminating a fault in Distribution network and optimizing a fault area
- SF6 gas Insulated Vacuum Interrupter
- KT, NT Certificate and Korean World-Class Product Award for Magnetic Actuator Mechanism
- Built-In RTU Digital Controller
|
| Characteristics |
| |
- The first Independent Technology in Korea and certified by KEMA Type Test
- Locally Manufacturing the most advanced Magnetic Actuator mechanism that is digitally controlled
- High reliability
- Reducing the number of parts by using Magnetic Actuator mechanism (About 170 parts to about 20 parts)
- Increasing the reliability
- Compact and light weight design
- Huge reduction of weight (470kg - 160kg)
- 15/27/38kV all products Type tested in KEMA, CESI Type Test Certificate and awarded from Korean World-Class Product Award.
|
|
Item
|
Rating
|
Item
|
Rating
|
|
Rated Current(A)
|
630
|
Basic Impulse withstand voltage (kV 1.2x50?)
|
110/150/170
|
|
Rated Voltage(kV)
|
15/27/38
|
Control cubicle
|
Operation voltage
|
AC220V Single phase
|
|
Frequency
|
50/60
|
Control power
|
DC24V
|
|
Short circuit
|
12.5(R.M.S.)
|
Permeable
|
85~110%
|
|
interrupting current(kA)
|
|
Voltage
|
|
|
Making current capacity (kA)
|
32.5 (Peak)
|
Power frequency withstand voltage
|
2kV 1 minute
|
|
Opening time(Cycle)
|
3.0 (0.05sec)
|
Basic Impulse withstand voltage
(kV 1.2x50?)
|
6kV, 3kA
|
|
Closing time(Cycle)
|
5 (0.1sec)
|
Weight (kg)
|
Tank
|
150/160/170
|
|
Power frequency withstand
voltage(kV)
|
Dry :50/60/70
Wet :45/50/60
|
Control cubicle
|
65/80
|
|
Communication port
|
RS232, RS485/422
|
|
Standard gas pressure : 0.5kg / ? G
|
|
Product Guide:
Reposted for informational purposes only. Views are not ours. Stay tuned for more.